Abstract
After a series of tests on various filter media, using 6 stripping methods, 2 methods were identified that met the criteria in the first objective. The first, a magnetic stirrer method is a mechanical agitation method and the second, referred to as the cylinder inversion method, is a manual agitation method. Each of these methods was chosen on the basis of their operator and speed-of agitation independence.
The criteria in the second objective were met by an in-depth suspended solids (SS) analysis performed on the filter media residue, with the total mass of solids removed from the media quantitatively separated on the grounds of acid solubility and volatility at 550oC. Standard Methods (1985) 209C and 209D were applied to the sample, with and without acid addition, in order to characterise the total filter media residue using 4 groupings: Soluble, non-volatile; soluble, volatile; non-soluble, non-volatile; and non-soluble, volatile.
By meeting the criteria of these 2 objectives, the previous non-specific suggestions in the literature have been improved to suggest the performing of tests in a well-specified, uniform way, the results of which can be internally compared.
Water SA Vol.30(1): 81-88